Carregant...
Miniatura

Tipus de document

Article

Versió

Versió acceptada

Data de publicació

Tots els drets reservats

Si us plau utilitzeu sempre aquest identificador per citar o enllaçar aquest document: https://hdl.handle.net/2445/227735

Microbial and physicochemical parameters associated with Legionella contamination in hot water recirculation systems

Títol de la revista

Director/Tutor

ISSN de la revista

Títol del volum

Resum

Hot water recirculation systems (HWRS) in hotels and nursing homes, which are common in countries such as Spain, have been related to outbreaks of legionellosis. To establish the relationships of microbial and physicochemical parameters, especially protozoa, with the occurrence of Legionella in HWRS, 231 samples from hotels and nursing homes were analysed for Legionella, protozoa, heterotrophic plate counts (HPC) at 22 and 37 °C, Pseudomonas, metals, temperature and others. Legionella pneumophila was the dominant species isolated, and 22 % were sg. 1. The sampling method became particularly important in order to define which factors were involved on the occurrence of Legionella. Results showed that the bacteria and the accompanying microbiota were more abundant in the first flush water whose temperature was lower. The bacteria occurred in those samples with high HPC and were inversely correlated with high temperatures. Multivariate regression showed that a concentration above 1× 105CFU/100 mL of HPC at 37 °C, Fe above 0.095 ppm and the presence of protozoa increased significantly the risk of Legionella colonization, while univariant regression showed that the presence of Cu above 0.76 ppm and temperature above 55 °C diminished it. Therefore, to reduce the risk associated with Legionella occurrence in HWRS these parameters should be taken into consideration.

Citació

Citació

SERRANO SUÁREZ, Alejandra, DELLUNDÉ, Jordi, SALVADÓ I CABRÉ, Humbert, CERVERO ARAGÓ, Sílvia, MÉNDEZ VIERA, Javier, CANALS, Oriol, BLANCO, Silvia, ARCAS PONS, Antoni, ARAUJO BOIRA, Rosa ma.. Microbial and physicochemical parameters associated with Legionella contamination in hot water recirculation systems. _Environmental Science and Pollution Research_. 2013. Vol. 20, núm. 5534-5544. [consulta: 9 de març de 2026]. ISSN: 0944-1344. [Disponible a: https://hdl.handle.net/2445/227735]

Exportar metadades

JSON - METS

Compartir registre