Early fire detection based on gas sensor arrays: Multivariate calibration and validation

Títol de la revista

Director/Tutor

ISSN de la revista

Títol del volum

Resum

Smouldering fires are characterized by the production of early gas emissions that can include high levels of CO and Volatile Organic Compounds (VOCs) due to pyrolysis or thermal degradation. Nowadays, standalone CO sensors, smoke detectors, or a combination of these, are standard components for fire alarm systems. While gas sensor arrays together with pattern recognition techniques are a valuable alternative for early fire detection, in practice they have certain drawbacks—they can detect early gas emissions, but can show low immunity to nuisances, and sensor time drift can render calibration models obsolete. In this work, we explore the performance of a gas sensor array for detecting smouldering and plastic fires while ensuring the rejection of a set of nuisances. We conducted variety of fire and nuisance experiments in a validated standard fire room (240 m3). Using PLS-DA and SVM, we evaluate the performance of different multivariate calibration models for this dataset. We show that calibration models remain predictive after several months, but perfect performance is not achieved. For example, 4 months after calibration, a PLS-DA model provides 100% specificity and 85% sensitivity since the system has difficulties in detecting plastic fires, whose signatures are close to nuisance scenarios. Nevertheless, our results show that systems based on gas sensor arrays are able to provide faster fire alarm response than conventional smoke-based fire alarms. We also propose the use of small-scale fire experiments to increase the number of calibration conditions at a reduced cost. Our results show that this is an effective way to increase the performance of the model, even when evaluated on a standard fire room. Finally, the acquired datasets are made publicly available to the community.

Descripció

Reproducció del document publicat a: https://doi.org/10.1016/j.snb.2021.130961

Matèries (anglès)

Citació

Citació

SOLORZANO SORIA, Ana maria, EICHMANN, Jens, FERNÁNDEZ ROMERO, Luis, ZIEMS, Bernd, JIMÉNEZ SOTO, Juan manuel, MARCO COLÁS, Santiago, FONOLLOSA MAGRINYÀ, Jordi. Early fire detection based on gas sensor arrays: Multivariate calibration and validation. _Sensors and Actuators B: Chemical_. 2021. Vol. 352, núm. 1. [consulta: 20 de gener de 2026]. ISSN: 0925-4005. [Disponible a: https://hdl.handle.net/2445/181024]

Exportar metadades

JSON - METS

Compartir registre